HART-Ready Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver for Hazardous-Area Valve Positioners, I/P Converters, and Line Fault Monitoring

News November 23, 2026

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver for HART Valve Positioners with Line Fault Monitoring

KFD2-SCD2-Ex1.LK is a single-channel isolated barrier for driving SMART I/P converters, electrical valves, and positioners installed in hazardous areas. It transfers the control current across galvanic isolation while allowing compatible HART communication to pass in both directions. Line fault detection helps the control system identify an open or short field circuit instead of treating every abnormal current as a process condition.


P+F KFD2-HMM-16


Product focus
 One isolated 4-20 mA control channel, 24 V DC Power Rail supply, hazardous-area field output, HART transparency, up to 650 ohm load capability, and integrated line fault monitoring.

Where the Module Sits in the Valve Loop

Loop sectionRole
DCS or safety controllerGenerates the analogue command and may supervise the circuit for alarm conditions.
KFD2-SCD2-Ex1.LKIsolates the circuits, limits hazardous-area energy, repeats current, and transfers HART data.
Positioner or I/P converterConverts the control signal into pneumatic pressure or valve movement.

Fault Behavior That Supports Faster Diagnosis

Field conditionModule responseMaintenance meaning
Normal loopControl current is repeated to the field device.Valve command and HART communication remain available.
Lead breakThe control-side input presents a high impedance and the red fault LED flashes.Check open terminals, cable damage, and disconnected field equipment.
Field short circuitThe module limits field current and signals a fault condition.Inspect cable insulation, junction boxes, and field-device terminals.

HART Communication Details

Digital HART information is superimposed on the analogue current and transferred bidirectionally. Integrated test sockets support connection of a HART communicator. When the loop resistance is too low, the documented internal resistance can be included through the designated terminals. For positioners that do not fully follow the HART standard, the SMART function can be changed according to the product instructions.

Replacement Review

Exact suffix
Keep the complete KFD2-SCD2-Ex1.LK designation.
Load calculation
Confirm available loop voltage and the field-device load.
Fault monitoring
Verify whether the controller expects line-break and short-circuit signaling.

Also check terminal assignments, Power Rail supply, hazardous-area classification, HART requirement, and the latest functional-safety documentation. A clear photo of the installed label and wiring is useful when confirming the exact replacement.

Related Pepperl+Fuchs Models

KFD2-SCD2-Ex2.LK, KFD2-SCD-Ex1.LK, KCD2-SCD-Ex1, KFD2-CD-Ex1.32, KFD2-CD2-Ex1, KFD2-CD2-Ex2, KFD0-CS-Ex1.51P, KFD0-CS-Ex2.50P, KFD2-STC5-Ex1, KFD2-STC4-Ex1.2O, KFD2-CRG2-Ex1.D, KFD2-GUT-Ex1.D, KFD2-WAC2-Ex1.D, KFD2-EB2, and KCD2-STC-Ex1.ES.