Pepperl+Fuchs HiC2832R1 Two-Channel Switch Amplifier for NAMUR Inputs, Line Fault Transparency, and H-System Termination Boards

Pepperl+Fuchs HiC2832R1 is a two-channel H-System switch amplifier designed to connect hazardous-area NAMUR sensors or dry contacts with application-specific digital input circuits in the safe area. It mounts directly on a compatible termination board, receives power through the board, and provides two passive transistor outputs for fast and organized signal transfer inside process control and safety system cabinets.

 Pepperl-Fuchs-HiC2832R1-800x600


 

2 channels
Compact dual digital input processing
NAMUR / contact
Field input compatibility
2 passive outputs
Resistive transistor signals
SIL 2, SC 3
Functional-safety capability

How HiC2832R1 Fits into the Signal Path

Signal-path sectionFunction
Hazardous-area fieldNAMUR sensors or volt-free contacts report position, level, limit, or machine status.
HiC2832R1 moduleProvides intrinsic-safety separation, interprets input current, and monitors field wiring.
Termination boardSupplies 19 to 30 V DC and routes field, output, and fault-bus connections.
Control or safety systemReceives the two passive transistor output states and diagnostic behavior.

Line Fault Transparency Makes Diagnostics More Useful

HiC2832R1 detects both lead breakage and short-circuit conditions in compatible NAMUR circuits. Line fault transparency allows the output behavior to distinguish a wiring fault from an ordinary process state when the connected control-system input supports the required resistive signal levels. A separate open-collector fault output also communicates internal fault information through the H-System fault bus.

Typical fault thresholds
 Lead break: field current at or below approximately 0.1 mA
 Short circuit: field current at or above approximately 6.5 mA
 Normal switching range: evaluated around the NAMUR switching point with defined hysteresis

Configuration and Replacement Checks

DIP switches allow the mode of operation to be reversed and line fault detection to be enabled or disabled according to the loop design. Before replacing a module, record the switch positions, termination-board model, slot location, output-card type, and field sensor arrangement. The coding pins and board connection must match; HiC2832R1 is not a general DIN-rail K-System module.

Also confirm the complete catalog number, part number 230983, hazardous-area approval, required SIL documentation, and whether the control input is designed for the passive resistive outputs. A clear photo of the front label and the termination-board reference reduces the risk of selecting a visually similar HiC2832 variant with different output behavior.

Related H-System Models

Product ModelProduct Description
HiC2832R1Two-channel switch amplifier with application-specific passive outputs
HiC2832Two-channel H-System switch amplifier
HiC2832R2Related variant with a different system-specific output interface
HiC2832R3Related dual-channel switch-amplifier version
HiC2025ESH-System SMART transmitter power supply